The Series 605 Magnehelic® Indicating Transmitter provides for both visual monitoring and electronic control of very low differential pressure. The Series 605 is ideal for control applications in building HVAC systems where local indication is desired during routine maintenance checks or necessary when trouble shooting the system. The easily read dial gage is complimented by the two-wire, 4-20 mA control signal utilizing the time-proven Dwyer® Magnehelic® gage mechanical design and Series 600 transmitter technology. The two-wire design with terminal strip on the rear simplifies connection in any 4-20 mA control loop powered by a 10-35 VDC supply.

 

GAGE SPECIFICATIONS

Service: Air and non-combustible, compatible gases

Wetted Materials: Consult factory

Accuracy: See Ordering page

Stability: ±1% F.S./yr

Pressure Limits: See Ordering page

Temperature Limits: 20 to 120°F (-6.67 to 48.9°C)

Process Connections: 1/8" female NPT

Size: 4" (101.6 mm) dial face, 5" (127 mm) O.D. x 2-11/16" (68.3 mm)

Weight: 1 lb, 12.6 oz (811 g)

Agency Approvals: CE

TRANSMITTER SPECIFICATIONS

Accuracy: See Ordering page (includes linearity, hysteresis, repeatability)

Temperature Limits: 20 to 120°F(-6.67 to 48.9°C)

Compensated Temperature Range: 32 to 120°F (0 to 48.9°C)

Thermal Effect: ±0.025% F.S./°F (0.045% F.S./°C)

Power Requirements: 10-35 VDC (2-wire)

Output Signal: 4 to 20 mA

Zero and Span Adjustments: Protected potentiometers

Loop Resistance: DC; 0-1250 ohms maximum

Current Consumption: DC; 38 mA maximum

Electrical Connections: Screw terminal block

Mounting Orientation: Diaphragm in vertical position. Consult factory for other position orientations.